EasyManuals Logo

Danfoss VLT Micro Drive FC 51 Quick Guide

Danfoss VLT Micro Drive FC 51
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
1.6 Troubleshooting
1.6.1 Warnings and Alarms
Number Description Warning Alarm Trip
Lock
Error Cause of problem
2 Live zero error X X Signal on terminal 53 or 60 is less than 50% of the value set
in:
parameter 6-10 Terminal 53 Low Voltage
parameter 6-12 Terminal 53 Low Current
parameter 6-22 Terminal 54 Low Current
4
Mains phase loss
1)
X X X Missing phase on supply side, or too high voltage imbalance.
Check supply voltage.
7
DC over voltage
1)
X X DC-link voltage exceeds the limit.
8
DC under voltage
1)
X X DC-link voltage drops below the voltage warning limit.
9 Inverter overloaded X X More than 100% load for too long.
10 Motor ETR overtemperature X X Motor is too hot. The load has exceeded 100% for too long.
11 Motor thermistor overtem-
perature
X X Thermistor or thermistor connection is disconnected.
12 Torque limit X Torque exceeds value set in either parameter 4-16 Torque Limit
Motor Mode or 4-17Torque Limit Generator Mode.
13 Overcurrent X X X Inverter peak current limit is exceeded.
14 Ground fault X X X Discharge from output phases to ground.
16 Short Circuit X X Short circuit in motor or on motor terminals.
17 Control word time-out X X No communication to frequency converter.
25 Brake resistor short-circuited X X Brake resistor is short-circuited, thus the brake function is
disconnected.
27 Brake chopper short-circuited X X Brake transistor is short-circuited, thus the brake function is
disconnected.
28 Brake check X Brake resistor is not connected/working.
29 Power board over temp X X X Heat sink cut-out temperature has been reached.
30 Motor phase U missing X X Motor phase U is missing. Check the phase.
31 Motor phase V missing X X Motor phase V is missing. Check the phase.
32 Motor phase W missing X X Motor phase W is missing. Check the phase.
38 Internal fault X X Contact local Danfoss supplier.
44 Ground fault X X Discharge from output phases to ground.
47 Control Voltage Fault X X 24 V DC is overloaded.
51 AMA check U
nom
and I
nom
X Wrong setting for motor voltage and/or motor current.
52 AMA low I
nom
X Motor current is too low. Check settings.
59 Current limit X Frequency converter overload.
63 Mechanical Brake Low X Actual motor current has not exceeded the release brake-
current within the start delay-time window.
80 Frequency Converter Initialised
to Default Value
X All parameter settings are initialised to default settings.
84 The connection between
frequency converter and LCP is
lost
X No communication between LCP and frequency converter.
85 Key disabled X See parameter group 0-4* LCP.
86 Copy fail X An error occurred while copying from frequency converter to
LCP, or from LCP to frequency converter.
87 LCP data invalid X Occurs when copying from LCP if the LCP contains erroneous
data - or if no data was uploaded to the LCP.
Quick Guide
VLT
®
Micro Drive FC 51
20 Danfoss A/S © 05/2016 All rights reserved. MG02BB4P
11

Table of Contents

Other manuals for Danfoss VLT Micro Drive FC 51

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Specifications

General IconGeneral
EnclosureIP20
Output Voltage0-100% of supply voltage
AltitudeUp to 1000 m without derating
Power Range0.18-22 kW
Control MethodV/f
CommunicationModbus RTU
Protection FeaturesOver-voltage, under-voltage, over-current, over-temperature
Ambient Temperature-10°C to 50°C
Storage Temperature-25°C to 65°C
Relative Humidity5-95% (non-condensing)
Input Voltage200-240 V, 380-480 V
Braking FunctionIntegrated braking chopper (optional)

Related product manuals