Chapter 14 Troubleshooting
14-13
14
problem by means of the related flag in the
program.
6108 SMTP verification failed
Check for the correct ID/Password and set up in
HWCONFIG > CPU Module > Device Setting >
Options > Ethernet Port Advanced > Email again.
SM1113
X
6200
The remote communication IP address
set in the TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6201
The local communication port set in the
TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6202
The remote communication port set in
the TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6203
The device from which the data is sent
in the TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6206
The device which receives the data in
the TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6208
The data received through the TCP
socket exceeds the device range.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > TCP
Socket.
- X
6209
The remote communication IP address
set in the UDP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
- X
620A
The local communication port set in the
UDP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module
in HWCONFIG CPU Module > Device Setting >
Options > Ethernet Port Advanced > UDP
Socket.
- X

Table of Contents

Other manuals for Delta DVP-ES3 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta DVP-ES3 Series and is the answer not in the manual?

Delta DVP-ES3 Series Specifications

General IconGeneral
BrandDelta
ModelDVP-ES3 Series
CategoryController
LanguageEnglish

Related product manuals