_14
Error
code
Description
CPU
status
ERROR LED indicator status
ON
Blinking
fast
Blinking
normally
Blinking
slowly
OFF
200B
The operand n or the other constant operands K/H
exceed the range.
Continue V
200C
The operands overlap.
Continue
V
200D
The binary to binary-
coded decimal conversion is
incorrect.
Continue V
200E The string does not end with 00. Continue V
2012
Incorrect division operation
Continue
V
2013
The value exceeds the range of values which can
be represented by the floating-point numbers.
Continue V
2014
The task designated by the TKON or YKOFF
instruction is incorrect, or exceeds the range.
Continue V
2017
The instruction BREAK is written outside of the
FOR-NEXT loop.
Continue V
2027
No such position planning table number or the
format is incorrect.
Continue V
2028
The high speed output instruction is being
executed. Only one instruction can be executed at a
time.
Continue V
6004
The IP address filter is set incorrectly.
Continue
V
600D
RJ45 port is not connected.
Continue
V
6010
The number of the MODBUS TCP connections
exceeds the range.
Continue V
6011
The number of the EtherNet/IP connections
exceeds the range.
Continue V
6012
There are devices using the same IP address.
Continue
V
6100
The email connection is busy.
Continue
V
6103
The trigger attachment mode in the email is set
incorrectly.
Continue V
6104
The attachment in the email does not exist.
Continue
V
6105
The attachment in the email is too big.
Continue
V
6106
There is an SMTP server response timeout.
Continue
V
6107
There is an SMTP server response timeout.
Continue
V
6108
SMTP verification failed
Continue
V
6200
The remote communication IP address set in the
TCP socket function is illegal.
Continue V
6201
The local communication port set in the TCP socket
function is illegal.
Continue V
6202
The remote communication port set in the TCP
socket function is illegal.
Continue V
6203
The device from which the data is
sent in the TCP
socket function is illegal.
Continue V
6206
The device that receives the data in the TCP socket
function is illegal.
Continue V
6208
The data that is received through the TCP socket
exceeds the device range.
Continue V

Table of Contents