DVP-ES3/EX3/SV3/SX3 Series Hardware and Operation Manual
2-22
Model
Item
DVP28SV311R
DVP28SV311S
DVP20SX311R
DVP20SX311S
Analog input mode N/A
-10V~10V; -20mA~20mA; 4mA~20mA;
Analog linearity
deviation
N/A
Normal temperature environment:
±0.5%; All temperature environment:
Analog input
N/A
≧1MΩ (Voltage mode)
Analog input isolation
When there is isolation between analog and digital electricals and there is no
isolation among analog channels.
Isolation between digital electrical and grounding: 500 VAC
Isolation between analog and digital electrical: 500 VAC
Isolation between analog electrical and grounding: 500 VAC
Isolation between 24 VDC and grounding: 500 VAC
*
1
: Analog input data updates automatically in every PLC scan cycle.