EasyManua.ls Logo

Delta M42U

Delta M42U
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 3-13: Location for DC terminals for 120 models
IN 1
IN 2
IN 1 IN 2
EMT
1½ " cable gland for DC with EMT
Stripping length: 10~11mm [0.40~0.43in]
Conductor cross-section: 12~10 AWG (4~6 mm²)
Torque 16 lbf-in (1.8 N.m) to fix the screw
½" Opening for PE
2" cable gland for DC with EMT
- Ensure all fuse holder terminals are tightened to the specified torque value of
16 lbf-in (1.8 N.m).
ATTENTION
Ensure the DC conductors used are Cu and sized to the correct ampacity per
NEC or other local code
• Strip off all wires for 10~11 mm [0.4~0.43 in].
• The cross-sectional area for each DC conductor is 12~10 AWG.
• Ensure the fuse holder terminal clamp is open
• Ensure correct conductor is connected to the correct fuse holder.
Tighten each individual screw terminal screw to a torque value of 16 lbf-in
(1.8 N.m).
• Two 2” chassis access holes (KOs) can be utilized to connect conduits from
PV array DC wiring into the inverter, as shown in Figure 3-13.
120 models is compatible with 1000V/20A UL listed fuse.
Please read the following instructions for connecting DC terminals (120 models):
3.4.1 DC Wiring Installation for 120 models
AC Switch
Input 1 Fuse holders Input 2 Fuse holders
38
Installation

Table of Contents

Related product manuals