  When Pr.03-05 is set to 0, the analog output voltage is directly proportional to the output 
frequency of the AC motor drive. With Pr.03-06 set to 100%, the Maximum Output Frequency 
(Pr.01-00) of the AC motor drive corresponds to +10VDC on the AFM output. 
  Similarly, if Pr.03-05 is set to 1, the analog output voltage is directly proportional to the output 
current of the AC drive. With Pr.03-06 set to 100%, then 2.5 times the rated current 
corresponds to +10VDC on the AFM output.  
NOTE
 
Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 volts, 
the parameter 03-06 should be set using the following formula: 
Pr. 03-06 = ((meter full scale voltage)/10) x 100% 
For Example: When using the meter with full scale of 5 volts, adjust Pr.03-06 to 50%. If 
Pr.03-05 is set to 0, then 5VDC will correspond to Maximum Output Frequency. 
 
03 - 07  Digital Output Multiplying Factor  Unit: 1
  Settings  01 to 20 times  Factory Setting: 01
  This parameter determines the multiplying factor for the AC drives digital output frequency at 
the digital output terminals (DFM-DCM). The pulse frequency is equal to the AC motor drive 
output frequency multiplied by Pr.03-07. (Pulse frequency = actual output frequency x Pr.03-07) 
 
03 - 08  Terminal Count Value   Unit: 1
  Settings  00 to 65500  Factory Setting: 00
  This parameter sets the count value of the internal counter. The external terminal TRG  
increases the internal counter. Upon completion of counting, the specified output terminal will 
be activated. (Pr.03-00 to Pr.03-03 set to 14). 
  When the display shows c5555, the drive has counted 5,555 times. If display shows c5555•, it 
means that real counter value is between 55,550 to 55,559. 
 
03 - 09   Preliminary Count Value  Unit: 1
  Settings  00 to 65500  Factory Setting: 00