Chapter 5 Parameters|VFD-B Series 
Revision July 2008, BE16, SW V4.08 & V5.00  5-53 
04 - 04  Multi-function Input Terminal (MI1)  
    Factory Setting: 01
04 - 05  Multi-function Input Terminal (MI2)  
    Factory Setting: 02
04 - 06  Multi-function Input Terminal (MI3)  
    Factory Setting: 03
04 - 07  Multi-function Input Terminal (MI4)  
    Factory Setting: 04
04 - 08  Multi-function Input Terminal (MI5)  
    Factory Setting: 05
04 - 09  Multi-function Input Terminal (MI6)  
    Factory Setting: 06
 
Settings Function  Description 
00 No Function 
Any unused terminals should be programmed to 0 to 
insure they have no effect on operation. 
01  Multi-Step Speed Command 1
02  Multi-Step Speed Command 2
03  Multi-Step Speed Command 3
04  Multi-Step Speed Command 4
These four inputs select the multi-speed defined by 
Pr.05-00 to Pr.05-14 as shown in the diagram at the 
end of this table. 
 
NOTE: Pr.05-00 to Pr.05-14 can also be used to 
control output speed by programming the AC motor 
drive’s internal PLC function. There are 17 step 
speed frequencies (including Master Frequency and 
Jog Frequency) to select for application. 
05 External Reset (N.O.) 
The External Reset has the same function as the 
Reset key on the Digital keypad. After faults such as 
O.H., O.C. and O.V. are cleared this input can be 
used to reset the drive. 
06 Accel/Decel Inhibit 
When the command is active, acceleration and 
deceleration is stopped and the AC motor drive 
maintains a constant speed. 
07 
Accel/Decel Time Selection 
Command 1 
08 
Accel/Decel Time Selection 
Command 2 
Used to select the one of four Accel/Decel Times 
(Pr.01-09 to Pr.01-12, Pr.01-18 to Pr.01-21). See 
explanation at the end of this table.