Chapter 5 Parameters|VFD-B Series
5-38 Revision July 2008, BE16, SW V4.08 & V5.00
02 - 04 Motor Direction Control
Factory Setting: 00
Settings 00 Enable Forward/Reverse operation
01 Disable Reverse operation
02 Disabled Forward operation
The parameter determines the AC motor drive direction of rotation. See Chapter 2 for definition
of direction of rotation.
02 - 05 2-wire/ 3-wire Operation Control Modes
Factory Setting: 00
Settings 00 2-wire: FWD/STOP, REV/STOP
01 2-wire: FWD/REV, RUN/STOP
02 3-wire Operation
There are three different types of control modes:
02-05
External Terminal
00
2-wire
FWD /STOP
REV / STOP