Chapter 5 Parameters|VFD-B Series 
5-70  Revision July 2008, BE16, SW V4.08 & V5.00 
06 - 15  Under-Current Detection Restart Delay Time  Unit: 1
  Settings  1~600 min  Factory Setting: 10
  If output current is lower than the setting Pr.06-12 for a time that exceeds Pr.06-13 setting 
during operation, the AC drive will warn per Pr.06-14 setting. If Pr.06-14 is set to 03, the AC 
drive will restart after the delay time set by Pr.06-15 is up. 
 
06 - 16  User-Defined Low-Voltage Detection Level (Lv)  Unit: 1
 Settings 00  Disabled 
    230V series: 220 ~ 300VDC  Factory Setting: 00
    460V series: 440 ~ 600VDC  Factory Setting: 00
    575V series: 520 ~ 780VDC  Factory Setting: 00
06 - 17  User-Defined Low-Voltage Detection Time  Unit: 0.1
  Settings  0.1~ 3600.0 sec  Factory Setting: 0.5
  When the DC BUS voltage is lower than the setting of Pr.06-16 for a time exceeding the 
setting of Pr.06-17, the AC motor drive will output a signal when Pr.03-00 ~ Pr.03-03 is set to 
28.
 
 
06 - 18  Reserved