Chapter 5 Parameters|VFD-B Series 
5-42  Revision July 2008, BE16, SW V4.08 & V5.00 
Group 3: Output Function Parameters 
03 - 00  Multi-function Output Relay (RA1, RB1, RC1) 
   
Factory Setting: 08
03 - 01  Multi-function Output Terminal MO1  
    Factory Setting: 01
03 - 02  Multi-function Output Terminal MO2 
    Factory Setting: 02
03 - 03  Multi-function Output Terminal MO3 
    Factory Setting: 20
 
Settings Function  Description 
00 No Function   
01  AC Drive Operational 
Active when there is an output from the drive or RUN 
command is “ON”. 
02 
Master Frequency 
Attained 
Active when the AC motor drive reaches the output 
frequency setting. 
03 Zero Speed 
Active when Command Frequency is lower than the 
Minimum Output Frequency. 
04 Over-Torque Detection 
Active as long as over-torque is detected. (Refer to Pr.06-03 
~ Pr.06-05) 
05 
Baseblock (B.B.) 
Indication 
Active when the output of the AC motor drive is shut off 
during baseblock. Base block can be forced by Multi-function 
input (setting 9 or 10). 
06  Low-Voltage Indication  Active when low voltage(Lv) is detected. 
07 
Operation Mode 
Indication 
Active when operation command is controlled by external 
terminal. 
08 Fault Indication 
Active when faults occur (oc, ov, oH, oL, oL1, EF, cF3, HPF, 
ocA, ocd, ocn, GFF). 
09 
Desired Frequency 
Attained 1 
Active when the desired frequency (Pr.03-04) is attained. 
10   PLC Program Running  Active when PLC Program is running. 
11 
PLC Program Step 
Completed 
Active for 0.5 sec each time the multi-step speed is attained.
12  PLC Program Completed
Active for 0.5 sec when the PLC program cycle has 
completed 
13  PLC Operation Paused  Active when PLC operation is paused.