EasyManua.ls Logo

Delta VFD-B - B.1.2 Specifications for Brake Unit; Order P;N: BR1 K0 W050, BR1 K2 W008, BR1 K2 W6 P8, BR1 K5 W005, BR1 K5 W040

Delta VFD-B
239 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B Accessories|VFD-B Series
B-6 Revision July 2008, BE16, SW V4.08 & V5.00
Order P/N: BR1K0W050, BR1K2W008, BR1K2W6P8, BR1K5W005, BR1K5W040
B.1.2 Specifications for Brake Unit
230V Series 460V Series
575V
Series
2015 2022 4030 4045 4132 5055
Max. Motor Power (kW)
15 22 30 45 132 55
Max. Peak Discharge Current
(A) 10%ED
40 60 40 60 240 60
Continuous Discharge Current
(A)
15 20 15 18 75 20
Output Rating
Brake Start-up Voltage (DC)
330/345/360/380
/400/415±3V
660/690/720/76
0/800/830±6V
618/642/667
/690/725/75
0±6V
950±8V
Input
Rating
DC Voltage 200~400VDC 400~800VDC
607~
1000VD
C
Heat Sink Overheat
Temperature over +95°C (203
o
F)
Alarm Output Relay contact 5A 120VAC/28VDC (RA, RB, RC)
Protection
Power Charge Display Blackout until bus (+~-) voltage is below 50VDC
Installation Location Indoor (no corrosive gases, metallic dust)
Operating Temperature
-10°C +50°C (14
o
F to 122
o
F)
Storage Temperature
-20°C +60°C (-4
o
F to 140
o
F)
Humidity 90% Non-condensing
Environment
Vibration
9.8m/s
2
(1G) under 20Hz
2m/s
2
(0.2G) at 20~50Hz
Wall-mounted Enclosed Type IP50 IP10 IP50