B.3.1.2 PG-02 Terminal Descriptions 
1. Terminals   
 
Terminal Symbols Descriptions 
VP 
Power source of PG-02 (FSW1 can be switched to 12V or 5V)  
Output Voltage: (+12VDC ±5% 200mA) or (+5VDC ±2% 400mA) 
DCM 
Power source (VP) and input signal (A, B) common 
 A-
,B-
B
 
Input signal from Pulse Generator. Input type is selected by FSW2. It 
can be 1-phase or 2-phase input. Maximum 500kP/sec (z-phase 
function is reserved). If the voltage exceeds 12V, it needs to use TP 
type with connecting the external current limiting resistor(R). The 
current should be within 5 to 15mA. 
The formal of current limiting resistor is: 
mA
R
VVin
mA 15
480
2
5 ≤
+Ω
≤
 
A/O, B/O 
PG-02 output signal for use with RPM Meter. (Open Collector) 
Maximum DC24V 100mA 
COM 
PG-02 output signal (A/O, B/O) common. 
2. Wiring Notes 
The control, power supply and motor leads must be laid separately.  They must not be fed 
through the same cable conduit / trunk. 
a.  Please use a shielded cable to prevent interference. Do not run control wires 
parallel to any high voltage AC power line (220 V and above).  
b.  Connect shielded wire to DCM 
 only. 
c.  Recommended wire size 0.21 to 0.81mm
2 
(AWG24 to AWG18). 
d. Wire length: 
Types of Pulse 
Generators 
Maximum Wire Length  Wire Gauge 
Output Voltage  50m 
Open Collector  50m 
Line Driver  300m 
Complementary 70m 
1.25mm
2 
(AWG16) or above