Chapter 5 Parameters|VFD-B Series 
5-24  Revision July 2008, BE16, SW V4.08 & V5.00 
00 - 02 
Parameter Reset  
        Factory Setting:  00
 Settings 08 Keypad Lock 
    09  All parameters are reset to factory settings (50Hz, 220V/380V/575V) 
    10  All parameters are reset to factory settings (60Hz, 220V/440V/575V) 
  This parameter allows the user to reset all parameters to the factory settings except the fault 
records (Pr.06-08 ~ Pr.06-11). 
50Hz: Pr.01-01 is set to 50Hz and Pr.01-02 is set to 230V, 400V or 575V. 
60Hz: Pr.01-01 is set to 60Hz and Pr.01-02 is set to 230V, 460V or 575V.
 
  When Pr.00-02=08, the VFD-PU01 keypad is locked. To unlock the keypad, set Pr.00-02=00. 
 
00 - 03 
Start-up Display Selection 
        Factory Setting: 00
 Settings 00 Display the frequency command value. (LED F) 
    01  Display the actual output frequency (LED H) 
    02  Display the content of user-defined unit (LED U) 
    03  Multifunction display, see Pr.00-04 
  04 FWD/REV command 
  This parameter determines the start-up display page after power is applied to the drive. 
 
00 - 04  Content of Multi-Function Display 
   
 
Factory Setting: 00
  Settings  00  Display the output current in A supplied to the motor 
 
  01 
Display the counter value which counts the number 
of pulses on TRG terminal 
 
  02 
When the PLC function is active, the current step and 
its remaining operation time in s are shown. 
 
  03 
Display the actual DC BUS voltage in VDC of the AC 
motor drive 
 
  04 
Display the output voltage in VAC of terminals U, V, W 
to the motor. 
 
  05 
Display the power factor angle in º of terminals U, V, W 
to the motor. 
 
  06 
Display the output power in kW of terminals U, V and W 
to the motor.