Chapter 5 Parameters|VFD-B Series
5-86 Revision July 2008, BE16, SW V4.08 & V5.00
06H: write single register
08H: loop detection
10H: write multiple registers
The available function codes and examples for VFD-B are described as follows:
(1) 03H: multi read, read data from registers.
Example: reading continuous 2 data from register address 2102H, AMD address is 01H.
ASCII mode:
Command message:
Response message:
STX ‘:’ STX ‘:’
‘0’ ‘0’
Address
‘1’
Address
‘1’
‘0’ ‘0’
Function
‘3’
Function
‘3’
‘2’ ‘0’
‘1’
Number of data
(Count by byte)
‘4’
‘0’ ‘1’
Starting data
address
‘2’ ‘7’
‘0’ ‘7’
‘0’
Content of starting
address
2102H
‘0’
‘0’ ‘0’
Number of data
(count by word)
‘2’ ‘0’
‘D’ ‘0’
LRC Check
‘7’
Content of address
2103H
‘0’
CR ‘7’
END
LF
LRC Check
‘1’
CR
END
LF
RTU mode:
Command message:
Response message:
Address 01H
Address 01H
Function 03H
Function 03H
21H Starting data
address
02H
Number of data
(count by byte)
04H
00H 17H Number of data
(count by word)
02H
Content of address
2102H
70H
CRC CHK Low 6FH 00H
CRC CHK High F7H
Content of address
2103H
00H
CRC CHK Low FEH
CRC CHK High 5CH
(2) 06H: single write, write single data to register.
Example: writing data 6000(1770H) to register 0100H. AMD address is 01H.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-B and is the answer not in the manual?

Delta VFD-B Specifications

General IconGeneral
SeriesVFD-B
Power Range0.4kW to 15kW
Control MethodV/F Control, Sensorless Vector Control
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
CommunicationRS-485
Protection FeaturesOver-voltage, Over-current, Overheat, Under-voltage, Ground fault, Short circuit