Chapter 5 Parameters|VFD-B Series 
5-46  Revision July 2008, BE16, SW V4.08 & V5.00 
  When the counter value reaches this value, the corresponding multi-function output terminal 
will be activated, provided one of Pr.03-00 to Pr.03-03 set to 15 (Preliminary Count Value 
Setting). This multi-function output terminal will be deactivated upon completion of Terminal 
Count Value Attained. 
  The timing diagram: 
Te r m i n al C o u nt Va l ue
(Pr. 03-00~Pr. 03-03=14)
Preliminary Count Value
(Pr. 03-00~Pr. 03-03=15)
Display
(Pr.00-04=01)
TRG
Counter Trigger
The width of trigger signal
should not be less than
2ms(<250 Hz) 
2msec
2msec
Ex:03-08=5,03-09=3
 
 
03 - 11  EF Active when Preliminary Count Value Attained 
      Factory Setting: 00
  Settings  00  Preliminary count value attained, no EF display 
    01  Preliminary count value attained, EF active 
  If this parameter is set to 01 and the desired value of counter is attained, the AC drive will treat 
it as a fault. The drive will stop and show the “cEF” message on the display. 
 
03 - 12  Fan Control 
      Factory Setting: 00
  Settings  00  Fan always ON 
    01  1 minute after AC motor drive stops, fan will be OFF 
    02  AC motor drive runs and fan ON, AC motor drive stops and fan 
OFF 
    03  Fan ON to run when preliminary heatsink temperature attained 
  This parameter determines the operation mode of cooling fan. 
 
03 - 13  Brake Release Frequency  Unit: 0.01
  Settings  0.00 to 400.00Hz  Factory Setting: 0.00
03 - 14  Brake Engage Frequency  Unit: 0.01
  Settings  0.00 to 400.00Hz  Factory Setting: 0.00
  These two parameters are used to set control of mechanical brake via the output terminals 
(MO1~MO3) when Pr.03-00~03-03 is set to 29. Refer to the following example for details.