Chapter 5 Parameters|VFD-B Series 
5-2  Revision July 2008, BE16, SW V4.08 & V5.00 
5.1 Summary of Parameter Settings 
: The parameter can be set during operation. 
Group 0 User Parameters 
Parameter Explanation  Settings 
Factory 
Setting
Customer
00-00  Identity Code of 
the AC motor drive 
Read-only ##  
00-01 Rated Current 
Display of the AC 
motor drive 
Read-only  #.#  
08: Keypad lock 
09: All parameters are reset to factory settings 
(50Hz, 220V/380V/575V) 
00-02 Parameter Reset 
10: All parameters are reset to factory settings 
(60Hz, 220V/440V/575V) 
00 
 
00: Display the frequency command value (LED 
F) 
01: Display the actual output frequency (LED H)
02: Display the content of user-defined unit 
(LED U) 
03: Multifunction display, see Pr.00-04 
00-03 
Start-up Display 
Selection 
04: FWD/REV command 
00 
 
00: Display output current (A) 
01: Display counter value (C) 
02: Display process operation (1.tt) 
03: Display DC-BUS voltage (
u
) 
04: Display output voltage (E) 
05: Output power factor angle (n) 
06: Display output power (P) 
07: Display actual motor speed (HU) 
08: Display the estimated value of torque as it 
relates to current (t) 
09: Display PG numbers/10ms (G) 
10: Display analog feedback signal value (b)(%)
11: Display AVI (U1.) (%) 
12: Display ACI (U2.) (%) 
13: Display AUI (U3.) (%) 
00-04 
Content of Multi 
Function Display 
14: Display the temperature of heat sink  (°C) 
00 
 
00-05 
User-Defined 
Coefficient K 
0.01 to 160.00  1.00
 
00-06  Software Version  Read-only  #.##  
00-07  Password Input  00 to 65535  00   
00-08  Password Set  00 to 65535  00   
00: V/f Control 
01: V/f + PG Control 
02: Vector Control 
00-09 Control Method 
03: Vector + PG Control 
00