Chapter 5 Parameters|VFD-B Series 
Revision July 2008, BE16, SW V4.08 & V5.00  5-25 
00 - 04  Content of Multi-Function Display 
  07 
Display the actual motor speed in rpm (enabled in 
vector control mode or PG (Encoder) feedback control) 
(LED H and LED U). 
 
  08 
Display the estimated value of torque in Nm as it relates 
to current. 
 
  09 
Display PG encoder feedback pulses/10ms. 
Display value= (rpm*PPR)/6000 (see note) 
 
    10  Display analog feedback signal value in %. 
 
  11 
Display the signal of AVI analog input terminal in %. 
Range 0~10V corresponds to 0~100%. (LED U) 
 
  12 
Display the signal of ACI analog input terminal in %. 
Range 4~20mA corresponds to 0~100%. (LED U) 
 
  13 
Display the signal of AUI analog input terminal in %. 
Range -10V~10V corresponds to 0~100%. (LED U) 
 
  14 
Display the temperature of heat sink in °C. 
 
  This parameter sets the display when Pr. 00-03 is set to 03. 
  Pr.00-04=09. The display value is (((rpm/60)*PPR)/1000ms)*10ms 
with rpm=motor speed in revs/min and PPR=encoder pulse per revolution 
  When the display shows the multi-function display (Pr.00-03=03), the user also can view other 
information by pressing the “LEFT” key 
 on the VFD-PU01 keypad. 
 
00 - 05  User Defined Coefficient K  Unit: 0.01
  Settings  0.01 to d 160.00  Factory Setting: 1.00
  The coefficient K determines the multiplying factor for the user-defined unit. 
The display value is calculated as follows: 
U (User-defined unit) = Frequency Command * K (Pr.00-05) 
H (actual output) = Actual output frequency * K (Pr.00-05) 
Example: 
A conveyor belt runs at 13.6m/s at motor speed 60Hz. 
K = 13.6/60 = 0.23  (0.226667 rounded to 2 decimals), therefore Pr.00-05=0.23 
With Frequency command 35Hz, display shows LED U and 35*0.23=8.05m/s. 
 (To increase accuracy, use K=2.27 or K=22.67 and disregard decimal point.)