Pg. 50
HA9 Manual V. 1.3
1019956
7.2 Lock Kick
1 Disconnect the mains.
2 Press the LEARN BUTTON (LRN) and keep it depressed.
3 Connect the mains.
4 Watch the ERROR LED, flash 5 times for 3 seconds each.
5 Release the LEARN BUTTON after 5 flashes (LED is out).
6 Identify the lock kick status
The ERROR LED flashes an amount of short flashes that correspond to the status number after a short pause the
LED will repeat the status number and so on.
7 Changing the status
8 If you push the LEARN BUTTON once, the status number will increase. When you have reached the highest status
number it will start at number one again.
Push the button until you get the requested lock kick status, 1 = Basic (default), 2 = Enhanced
Disconnect the mains
Next time you connect the mains the operator will use the new status setting.
7.3 Lock Unlock
1 Disconnect the mains.
2 Press the LEARN BUTTON (LRN) and keep it depressed.
3 Connect the mains.
4 Watch the ERROR LED, flash 6 times for 3 seconds each.
5 Release the LEARN BUTTON after 6 flashes (LED is out).
6 Identify the current lock unlocked status.
The ERROR LED flashes an amount of short flashes that correspond to the status number after a short pause the
LED will repeat the status number and so on.
7 Changing the status.
8 If you push the LEARN BUTTON once, the status number will increase. When you have reached the highest status
number it will start at number one again.
Push the button until you get the requested status, Lock is unlocked at
1= Lock is unlocked when door is not closed.
2= Lock is unlocked when door is 0-10 degrees from closed position, during opening.
Disconnect the mains. Next time you connect the mains the operator will use the new status setting.