Table E.3 450 VA Sources
Current Range (Resolution)
AC
1.5 Seconds
Transient
Continuous
15, 45, 90, 180 A rms (0.01 A)
7.5, 22.5 A (0.001 A), 45 A, 90 A rms (0.01 A)
DC
1.5 Seconds
Transient
Continuous
10 A (0.001 A), 30, 60, 120 ADC
(0.01 A)
5 A (0.001 A), 15, 30, 60 ADC (0.01 A)
General Specifications
E-2 72A-2337-01 Rev. B 11/05
General Specifications
Table E.4 provides you with general specifications for the F6300.
Table E.4 General Specifications
Specification Description
Source
Operation
Worst-case accuracy specifications simultaneously include all errors
contributed by variations in power line voltage, load regulation, stability,
and temperature, up to full output power. Includes stable source opera-
tion in four quadrants while delivering power — load power factor from
nearly 1 to 0, leading or lagging. Each F6000 Instrument is supplied with
a Certificate of Calibration traceable to the National Institute of Stan-
dards and Technology.
Electrostatic Dis-
charge Immunity
IEC 801-2 I.E.C. performance level 1 @ 10 kV: normal performance
within specifications. IEC 801-2 I.E.C. performance level 2 @ 20 kV:
no permanent damage.
Surge
Withstand
Capability
ANSI/IEEE C37.90. The F6000 Instrument functions as a source during
surge withstand capability tests, when the ANSI/IEEE-specified isolating
circuit is interposed between the instrument and the relay under test.
AC Amplitude
Accuracy at
50/60 Hz
From 20° to 30° C: < 0.02% typical or < 0.09 % Guaranteed
Typical of 0.02% of reading.
Distortion and
Noise at 50/60
Hz Output (10 Hz
- 2 KHz Band-
width)
Current Source: Total Harmonic Distortion (THD) < 0.02 % typical;
<0.1% guaranteed.