EasyManuals Logo

Dräger PIR 7000 Technical Handbook

Dräger PIR 7000
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
52
Maintenance
Maintenance
Maintenance Intervals
Observe EN 50073 and respective national regulations.
Daily
Visual inspection to determine readiness for operation – the green status light must be on.
While commissioning
During the automatic self-test, check the function of the yellow and green status lights.
Check zero-point calibration.
Check the current interface and if required also the HART
®
communication.
Check measuring value output and alarm activation by applying suitable test gas.
Prior to the inspection: Disable the alarm activation in the central device. Re-activate it when
the inspection is over.
At regular intervals,
that are to be determined by the persons responsible for the gas detection system –
recommended after 6 months:
Check the zero-point and sensitivity calibration (if necessary, temporarily disable the alarm
activation in the central device and re-activate it afterwards).
Check signal transmission to central device and alarm activation.
A calibration interval of more than 6 months is possible under the following conditions:
After an operation period of a maximum of six months, a check should be made of whether
an obstruction can occur in the gas entrance to the measuring cuvette within the given
application, e.g. due to dust, dirt, etc. If a restriction to the function caused by these effects
is excluded then the calibration interval can be prolonged – recommendation: Maximum
24 months.
Yearly
Inspection by competent personnel.
The inspection intervals are to be individually determined with regard to safety regulations,
process control conditions and device-related requirements.
We strongly recommend that a service contract be signed with Dräger Safety to have them
handle repairs and maintenance.

Table of Contents

Other manuals for Dräger PIR 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dräger PIR 7000 and is the answer not in the manual?

Dräger PIR 7000 Specifications

General IconGeneral
Detection PrincipleInfrared (IR)
Pressure Range700 to 1300 hPa
Ingress ProtectionIP66/67
Gases DetectedHydrocarbons
Measurement Range0 - 100 %LEL (Lower Explosive Limit) or 0 - 100 vol.%
Operating Temperature-40 to +65 °C
Output Signal4-20 mA
Housing MaterialStainless steel
CertificationsATEX, IECEx, UL, CSA
Response Timet90 ≤ 4 s

Related product manuals