Page #6 background image
6
Tests and Approvals
Tests and Approvals
The explosion-protection approvals are valid for the use of the gas transmitter in gas/vapour-air
mixtures of flammable gases and vapours or dust-air-mixtures of flammable dusts under
atmospheric conditions.
The explosion-protection approvals are not valid for use in oxygen enriched atmospheres.
_________________
1) The year of construction is indicated by the third letter of the serial number on the type plate:
Y = 2007, Z = 2008, A = 2009, B = 2010, C = 2011, etc.
example: serial number ARYH-0054, the third letter is Y, so the year of construction is 2007.
ATEX Type: IDS 01xx
Dräger Safety • 23560 Lübeck • Germany
0158
II 2G Ex d IIC T6/T4 – DEMKO 07 ATEX 0654417X
II 2D Ex tD A21 IP65 T80
o
C/T130
o
C PTB 07 ATEX 1016
–40
o
C Ta +40
o
C/+80
o
C
Year of construction (via serial number)
1)
IECEx Type: IDS 01xx
Dräger Safety • 23560 Lübeck • Germany
Ex d IIC T6/T4 – IECEx UL 07.0009X
Ex tD A21 IP65 T80
o
C/T130
o
C – IECEx PTB 07.0016
–40
o
C Ta +40
o
C/+80
o
C
Year of construction (via serial number)
1)
UL (Classified) Type: IDS 010x
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
Class I, Zone 1, Group IIC
T-Code T6/T4, –40
o
C Ta +40
o
C/+80
o
C
9 to 30 VDC, 9 W • Type 4X
CSA (C-US) Type: IDS 010x
Class I, Div. 1, Groups B, C, D
Class II, Div. 1, Groups E, F, G
Class I, Zone 1, Group IIB+H2
T-Code T6/T4, –40
o
C Ta +40
o
C/+80
o
C
C22.2 no. 152 (only Dräger PIR 7000)
9 to 30 VDC, 9 W • Type 4X
TÜV SIL 2 Certification
EN 61508, EN 50402

Table of Contents

Other manuals for Dräger PIR 7000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dräger PIR 7000 and is the answer not in the manual?

Dräger PIR 7000 Specifications

General IconGeneral
Detection PrincipleInfrared (IR)
Pressure Range700 to 1300 hPa
Ingress ProtectionIP66/67
Gases DetectedHydrocarbons
Measurement Range0 - 100 %LEL (Lower Explosive Limit) or 0 - 100 vol.%
Operating Temperature-40 to +65 °C
Output Signal4-20 mA
Housing MaterialStainless steel
CertificationsATEX, IECEx, UL, CSA
Response Timet90 ≤ 4 s