MGR10 A/B/C - Revision : I (for 7.0 software revision) 48
6-1-3 Logical states definition :
Input :
The high logical state is defined by a DC or AC voltage presence between the Umin and the
Umax values .
The low logical state is defined by no voltage .
Output :
The high logical state is defined by a closed contact .
The low logical state is defined by an opened contact .
6-1- 4 Connection :
All the IO lines are available on a female Sub-D type 25 pins connector on the unit rear panel .
1 Not connected
2 0 Volt
3 25 Volts DC protected by internal fuse ( 1AT)
4 Input for PLC option : CTRLIN
5 Input for PLC option : N1
6 Input for PLC option : N3
7 Input for PLC option : MES_DCH
8 Output Common : COM_OUT
9 Output for PLC option : FAIL HIGH
10 Output for PLC option : PASS
11 0-10 volts output , ground point
12 Frame
13 Not connected
14 Not connected
15 Not connected
16 Input Common : COM_IN
17 Input for PLC option : N0
18 Input for PLC option : N2
19 Not connected
20 Output for PLC option : FAIL LOW
21 Output for PLC option : CTRLOUT
22 Output for PLC option : EOT
23 Output for PLC option : ERROR
24 0-10 volts output , positive pole
25 Not connected