04/10 MN04020001Z-EN
Parameter menu (PAR)
85
21 Counter, value 2 reached. The counter value is f the trigger value
set at P3.22 and can be reset by activating P3.24.
22 RUN message active.
23 AL 50 - message (life-zero).
Message if the setpoint signal (life zero) of AI1 and/or AI2 is below
4 mA- or 2 V (P2.1 = 1, P2.5 = 1).
24 LOG function fulfilled.
Message if the logical operation of P13.3 is fulfilled (LOG = 1).
25 PID controller, actual value monitoring.
Message if the actual value is within the hysteresis set at P9.15
and P9.16.
26 External brake actuated.
Switch threshold: set value of P12.8.
27 Current monitoring
Switch threshold: set value of P5.8.
28 Fieldbus, remote output.
The assigned digital output is written directly to the general
control word (ID 2001, bit 13).
P5.2 314 / RO2 signal (relay output 2) 3
Assignment of the function same as P5.1.
P5.3 312 / DO Signal (Digital Output) 1
Assignment of the function same as P5.1.
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)