EasyManuals Logo

Eaton MMX34AA9D0 Series User Manual

Eaton MMX34AA9D0 Series
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #104 background imageLoading...
Page #104 background image
Parameters
04/10 MN04020001Z-EN
100
PID controller (P9)
The frequency inverters of the M-Max
TM
series are provided with
a PID controller that you activate with P9.1 = 1. The controller can
be deactivated via a digital input (DI6 in FS) P3.12 = 6.
h
PID control is superimposed on the frequency inverter
function. You should therefore set all of the frequency
inverter’s drive-related parameters, such as maximum
output frequency (motor speed), acceleration and
deceleration ramps (mechanical load, belts). Frequency
inverter and motor are process-integrated actuators. The
output frequency to the motor (which determines the
speed) is specified as manipulated variable from the PID
controller.
h
When the PID controller is activated, the setpoints and
actual values become process variables and are
normalized automatically into percentages (%). For
example, the specified setpoint (0 - 100 %) here is the
same as a volume flow (0 - 50 m3/h). The actual value
here is the volume flow (m3/h) from a suitable sensor,
which is evaluated again as a percentage (0 - 100 %).
If this process data is to be displayed in the physical
variable (m
3
/h), you can set the conversion with
parameter P9.19 (a “Display factor (P9.19)”).
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)
P9.1 163 / PID Controller 0
0 Deactivated
1 Activated for drive control.
2 Activated for external application.
P9.2 118 / PID controllers, P amplification 100
Setting range: 0.0 - 1000 %
Proportional Gain (KP)
Low values attenuate the control action.
High values can cause oscillation.
P9.3 119 / PID controller, I reset time 10.0
Setting range: 0.00 - 320.0 s
Integral time constant
P9.4 167 / PID controller, setpoint input via operating unit 0.0
Setting range: 0.0 - 100.0 %
P9.5 332 / PI controller, setpoint source 0
0 The setting range is limited by P6.3 (raised starting frequency) and
P6.4 (end frequency).
Potentiometer (keypad)
Frequency [Hz]
Process variable [%] with P9.1 = 1
1 Fieldbus
2 AI1
3 AI2
P9.6 334 / PID controller, actual value (PV) 2
0 Fieldbus
1 AI1 and S2, (a figure 39, page 43)
P2.1=0 (0mA/0V)
P2.1=1 (4mA/2V)
2 AI2 and S3, (a figure 39, page 43)
P2.5=0 (0mA/0V)
P2.5=1 (4mA/2V)
P9.7 336 / PID controller, actual value limiting, minimum 0.0
Setting range: 0.0 - 100.0 %

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton MMX34AA9D0 Series and is the answer not in the manual?

Eaton MMX34AA9D0 Series Specifications

General IconGeneral
BrandEaton
ModelMMX34AA9D0 Series
CategoryDC Drives
LanguageEnglish

Related product manuals