NZM-XDMI-DPV1
(PROFIBUS-DPV1 Interface for
DMI)
98
11/04 MN01219002Z-EN
Motor clockwise
rotation,
Motor
anticlockwise
rotation
00
01
10
Motor is switched off
Motor is switched on for
anticlockwise rotation
Motor is switched on for
clockwise rotation
Outputs 0 and 1 have been
parameterized for “reversing
starter” or
the outputs 0, 1, 2 and 3 have
been parameterized for “star-
delta-reversing starter”
Motor state
Is set if the Motor “ON” bit, motor
anticlockwise rotation or motor
clockwise rotation is set
Motor-starter function is
parameterized in DMI
Motor “ON” 0
1
Motor is switched off
Motor is switched on
Output 0 has been parameterized
to “direct-on-line starter” or
outputs 0, 2 and 3 have been
parameterized for “star-delta
starter”
Not used
No information for evaluation
Overload warning At least one phase current has exceeded
the overload 1 limit (I
r
= 100 %)
Ready to switch on
1 The circuit-breaker is switched off
(not tripped)
Star configuration 0
1
The motor will not be operated in
star configuration
The motor is operated in star
configuration
Outputs 0, 2, 3 have been
parameterized for “star-delta
starter” or
the outputs 0, 1, 2 and 3 have
been parameterized for “star-
delta-reversing starter”
Trip cause
(release reason)
000
001
010
011
100
101
110
no trip
I
r
I
i
I
sd
I
dn
selectivity, communication fault,
over-temperature, hardware fault
neutral pole overcurrent
Designation Meaning Precondition