5 Application example – CANopen fieldbus connection on DA1 variable frequency drives
5.2 Materials required
CANopen for DA1, DC1, DE11 09/16 MN040019EN www.eaton.com 67
A new node called DA1 (EDS) [VAR] will be added underneath the
CanMaster[Var] node.
Adjusting the CAN parameters
Now configure the CAN-specific parameters for the DA1 variable frequency
drive:
Click on the DA1 (EDS) [VAR] node and open the CAN parameters tab.
Enable the Nodeguarding checkbox.
Now open the Send PDO-Mapping tab.
Modify the properties for the PDO 0x1800 and PDO 0x1801 objects as
specified below:
Select the PDO 0x1800 object on the right pane and click on the
Properties button.
The Node ID must be identical to the DA1 variable frequency
drive address set with parameter P5-01.
Nodeguarding must be enabled in order to be able to detect
communication faults.