190
Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P10.1.14 1702 Saturation Trip Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Saturation fault occurs.
0 = Disable Auto bypass on Saturation fault
1 = Enable Auto bypass on Saturation fault
P10.1.15 1703 Under Temp Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an UnderTemp fault occurs.
0 = Disable Auto bypass on UnderTemp fault
1 = Enable Auto bypass on UnderTemp fault
P10.1.16 1704 EEPROM Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.17 1705 FRAM Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.18 1706 Watchdog Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Watchdog fault occurs.
0 = Disable Auto bypass on Watchdog fault
1 = Enable Auto bypass on Watchdog fault
P10.1.19 1707 Fan Cooling Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Fan Cooling fault occurs.
0 = Disable Auto bypass on Fan Cooling fault
1 = Enable Auto bypass on Fan Cooling fault
P10.1.20 1708 Keypad Com Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Keypad Communication
fault occurs.
0 = Disable Auto bypass on Keypad Communication fault
1 = Enable Auto bypass on Keypad Communication fault
P10.1.21 1709 Option Card Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.22 1710 RTC Clock Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.23 1711 Ctrl Board OverTemp Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when an Charge Switch fault occurs.
0 = Disable Auto bypass on Charge Switch fault
1 = Enable Auto bypass on Charge Switch fault
P10.1.24 1713 Fieldbus Fault Bypass Enable 1,2,3 RW
This parameter specifies whether an automatic switch to bypass when a Fieldbus fault occurs.
0 = Disable Auto bypass on Fieldbus fault
1 = Enable Auto bypass on Fieldbus fault
P10.1.25 2832 Op Cont Interlock Fault Bypass Enable 1,2,3 RW
This parameter enables an output contactor interlock fault to run in bypass.
P10.2.1 2476 Redundant Drive Enable 2,3 RW
Use this parameter to enable the Redundant drive setup where multiple drives can be connected via Para
communications to start if the main drive fails or runtime settings below expires.
P10.2.2 2278 Drive ID 2,3 RW
Use this parameter to set the drive address when using multi drive redundant mode, based off this id the
drive enables in the desired sequence and can be monitored at this drive ID value in the monitor screen.
P10.2.3 2477 Redundant Run Time Enable 2,3 RW
Use this parameter to enables the Run time limit for the Redundant drive mode so that drives will be cycled
based off the Run time limit value.