196
Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P12.2.5 1560 FB Process Data Output 5 Sel 1,2,3 RW
Use this parameter to accessing the Fieldbus Data Output Selections, parameter/monitor ID's can be
assigned to these registers and then read over the desired Fieldbus Network Word for Process Data.
Default Values for Process Data Out in Fieldbus(build table for below values)
Process Data Out1 - Output Frequency = ID 1
Process Data Out2 - Motor Speed = ID 2
Process Data Out3 - Motor Current = ID 3
Process Data Out4 - Motor Torque = ID 4
Process Data Out5 - Motor Power = ID 5
Process Data Out6 - Motor Voltage = ID 6
Process Data Out7 - DC Link Voltage = ID 7
Process Data Out8 - Active Fault Code = ID 28
see Communication Manual MN040010EN for more details.
P12.2.6 1561 FB Process Data Output 6 Sel 1,2,3 RW
Use this parameter to accessing the Fieldbus Data Output Selections, parameter/monitor ID's can be
assigned to these registers and then read over the desired Fieldbus Network Word for Process Data.
Default Values for Process Data Out in Fieldbus(build table for below values)
Process Data Out1 - Output Frequency = ID 1
Process Data Out2 - Motor Speed = ID 2
Process Data Out3 - Motor Current = ID 3
Process Data Out4 - Motor Torque = ID 4
Process Data Out5 - Motor Power = ID 5
Process Data Out6 - Motor Voltage = ID 6
Process Data Out7 - DC Link Voltage = ID 7
Process Data Out8 - Active Fault Code = ID 28
see Communication Manual MN040010EN for more details.
P12.2.7 1562 FB Process Data Output 7 Sel 1,2,3 RW
Use this parameter to accessing the Fieldbus Data Output Selections, parameter/monitor ID's can be
assigned to these registers and then read over the desired Fieldbus Network Word for Process Data.
Default Values for Process Data Out in Fieldbus(build table for below values)
Process Data Out1 - Output Frequency = ID 1
Process Data Out2 - Motor Speed = ID 2
Process Data Out3 - Motor Current = ID 3
Process Data Out4 - Motor Torque = ID 4
Process Data Out5 - Motor Power = ID 5
Process Data Out6 - Motor Voltage = ID 6
Process Data Out7 - DC Link Voltage = ID 7
Process Data Out8 - Active Fault Code = ID 28
see Communication Manual MN040010EN for more details.
P12.2.8 1563 FB Process Data Output 8 Sel 1,2,3 RW
Use this parameter to accessing the Fieldbus Data Output Selections, parameter/monitor ID's can be
assigned to these registers and then read over the desired Fieldbus Network Word for Process Data.
Default Values for Process Data Out in Fieldbus(build table for below values)
Process Data Out1 - Output Frequency = ID 1
Process Data Out2 - Motor Speed = ID 2
Process Data Out3 - Motor Current = ID 3
Process Data Out4 - Motor Torque = ID 4
Process Data Out5 - Motor Power = ID 5
Process Data Out6 - Motor Voltage = ID 6
Process Data Out7 - DC Link Voltage = ID 7
Process Data Out8 - Active Fault Code = ID 28
see Communication Manual MN040010EN for more details.
P12.2.9 2415 Standard Status Word Bit0 Function Select 1,2,3 RW
Use this parameter to select status indication of this bit0 to be read over the communication Standard Status
Word.
P12.2.10 2416 Standard Status Word Bit1 Function Select 1,2,3 RW
Use this parameter to select status indication of this bit1 to be read over the communication Standard Status
Word.
P12.2.11 2417 Standard Status Word Bit2 Function Select 1,2,3 RW
Use this parameter to select status indication of this bit2 to be read over the communication Standard Status
Word.
P12.2.12 2418 Standard Status Word Bit3 Function Select 1,2,3 RW
Use this parameter to select status indication of this bit3 to be read over the communication Standard Status
Word.