Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
P13.1.15 633 Keypad ACK Timeout 1,2,3 RW
This function allows the user to change the timeout of the Keypad acknowledgement time. This is the
communication performed between the control module and the keypad.
This would be adjusted when using long communication cables between drive and a keypad to delay
message timeouts.
Example:
Transfer delay between the frequency converter and the PC = 600 ms
• The value of HMI Acknowledge Timeout is set to 1200 ms (2 x 600, sending delay + receiving delay)
The corresponding setting shall be entered in the [Misc]-part of the file.
• It must also be considered that intervals shorter than the HMI Acknowledge Timeout time cannot be used
in frequency converter drive monitoring.
P13.1.16 634 Keypad Retry Number 1,2,3 RW
With this parameter you can set the number of times the drive will try to receive acknowledgement when
it has not been received within the acknowledgement time (HMI Acknowledge Timeout) or if the received
acknowledgement is faulty.
P13.1.17 626 Startup Wizard 1,2,3 RW
The Startup Wizard facilitates commissioning the PowerXL Series druve. If selected Enable, the Startup
Wizard prompts operator for the language and application desired, RTC time clock and then advances through
the start-up parameter list/Application Mini wizard in keypad. After completion it allows the user to go to the
Main menu or default page and this parameter is set to Disabled. The Startup Wizard is always enabled for
the initial power up of the PowerXL Series vfd. By setting this parameter to Disable without going through
the Startup Wizard it will disable it from being active on Start up. If user goes into Start Up Wizard after
completion or defaults drive the Startup wizard will be Enabled.
0 = Enabled
1 = Disabled
P13.1.18 2412 Jog Softkey Hidden 1,2,3 RW
Use this parameter to hide the jog function from the soft key buttons.
0 = Disable
1 = Enable
P13.1.19 2413 Reverse Softkey Hidden 1,2,3 RW
Use this parameter to hide the Reverse function from the soft key buttons.
0 = Disable
1 = Enable
P13.1.20 2424 Output Display Unit 1,2,3 RW
This parameter allows for selecting a desired unit and scaled output to be viewed in the monitor menu as
user output and reference display. Value is scaled based on the max value setting the min and max value.
0 = % 12 = m3/min 24 = gal/min 36 = PSI
1 = 1/min 13 = m3/h 25 = gal/h 37 = lb/in2
2 = rpm 14 = m/s 26 = lb/s 38 = HP
3 = ppm 15 = mbar 27 = lb/min 39 = deg F
4 = pps 16 = bar 28 = lb/h 40 = PA
5 = l/s 17 = Pa 29 = CFM 41 = WC
6 = l/min 18 = kPa 30 = ft3/s 42 = HG
7 = l/h 19 = mVs 31 = ft3/min 43 = ft
8 = kg/s 20 = kW 32 = ft3/h 44 = m
9 = kg/min 21 = deg C 33 = ft/s 45 = Hz
10 = kg/h 22 = GPM 34 = in wg 46 = Strokes/min
11 = m3/s 23 = gal/s 35 = ft wg
P13.1.21 2460 Output Display Unit Min 1,2,3 RW
Use this parameter to set the minimum scaled value when changing the display unit to a value other than the
default Hz.
P13.1.22 2425 Output Display Unit Max 1,2,3 RW
Use this parameter to set the maximum scaled value when changing the display unit to a value other than the
default Hz.
P13.1.23 75 Keypad Lock Password 1,2,3 RW
Keypad password, locks keypad with password.
P13.2.1 640 Keypad Software Version 1,2,3 RO
Keypad firmware Version