Appendix A—Description of parameters
POWERXL DH1 SERIES ADJUSTABLE FREQUENCY DRIVES MN040041EN—August 2019 www.eaton.com
Code Modbus ID Parameter Application RO/RW
M6.7 34 PID2 Feedback 2,3 RO
PI(D) Controller 2 actual value feedback, units will vary based on the PI(D) Controller 2 unit setting.
M6.8 36 PID2 Error Value 2,3 RO
PI(D) Controller 2 Error or difference from between the reference and feedback, units will vary based
on the PI(D) Controller 2 unit setting.
M6.9 38 PID2 Output 2,3 RO
PI(D) Controller output value in percentage.
M6.10 39 PID2 Status 2,3 RO
PI(D) Controller 2 status indication, indicates if drive is stopped, running in PID mode, or in
PID sleep mode.
M7.1 558 TC1, TC2, TC3 2,3 RO
Timer channel status of channel 1, 2 and 3. Timer channels are used within the RTC parameter
group settings.
M7.2 559 Interval 1 2,3 RO
Time interval 1 status. See the RTC parameters for checking Interval 1 setup, when setting is met the status
will go indicated on and when not met it will be off.
M7.3 560 Interval 2 2,3 RO
Time interval 2 status. See the RTC parameters for checking Interval 2 setup, when setting is met the status
will go indicated on and when not met it will be off.
M7.4 561 Interval 3 2,3 RO
Time interval 3 status. See the RTC parameters for checking Interval 3 setup, when setting is met the status
will go indicated on and when not met it will be off.
M7.5 562 Interval 4 2,3 RO
Time interval 4 status. See the RTC parameters for checking Interval 4 setup, when setting is met the status
will go indicated on and when not met it will be off.
M7.6 563 Interval 5 2,3 RO
Time interval 5 status. See the RTC parameters for checking Interval 5 setup, when setting is met the status
will go indicated on and when not met it will be off.
M7.7 569 Timer 1 2,3 RO
Timer 1 value in seconds, value counts up to set timer value. See the RTC parameter group for defined
Timervalue.
M7.8 571 Timer 2 2,3 RO
Timer 2 value in seconds, value counts up to set timer value. See the RTC parameter group for defined
Timervalue.
M7.9 573 Timer 3 2,3 RO
Timer 3 value in seconds, value counts up to set timer value. See the RTC parameter group for defined
Timervalue.
M8.1 2445 Output 1,2,3 RO
User defined output value that can be seen in a specific desired unit and scale factor based on the output
frequency. This value will be displayed in the format selected by parameter Para ID 2426 with a scale value
from parameter Para ID 2462 and 2427.
M8.2 2447 Reference 1,2,3 RO
User defined reference value that can be seen in the desired unit and scale factor based on the frequency
reference. This value will be displayed in the format selected by parameter Para ID 2426 with a scale value
from parameter Para ID 2462 and 2427.
M9.1 601 Total MWh Count 1,2,3 RO
Energy Consumption MWH Meter (not resettable)
M9.2 603 Total Power Day Count 1,2,3 RO
Total Time Power is on, Days count (not resettable)
M9.3 606 Total Power Hr Count 1,2,3 RO
Total time Power is on, Hr Count (not resettable)
M9.4 604 Trip MWh Count 1,2,3 RO
Energy Consumption MWH Meter(resettable)