Operation and parameterization 67
Manual econ sens3 Version 3.0
i(L3)
34
1034
Current (current value)
L3
A
p(L1)
36
1036
Active power (current value)
L1
kW
p(L2)
38
1038
Active power (current value)
L2
kW
p(L3)
40
1040
Active power (current value)
L3
kW
q(L1)
42
1042
Reactive power (current value)
L1
kvar
q(L2)
44
1044
Reactive power (current value)
L2
kvar
q(L3)
46
1046
Reactive power (current value)
L3
kvar
s(L1)
48
1048
Apparent power (current value)
L1
kVA
s(L2)
50
1050
Apparent power (current value)
L2
kVA
s(L3)
52
1052
Apparent power (current value)
L3
kVA
PF tot
54
1054
Power factor (current value)
L1,L2,L3
PF(L1)
56
1056
Power factor (current value)
L1
PF(L2)
58
1058
Power factor (current value)
L2
PF(L3)
60
1060
Power factor (current value)
L3
Hdu(L1)
62
1062
Voltage distortion (current value)
L1-N; THD
%
Hdu(L2)
64
1064
Voltage distortion (current value)
L2-N; THD
%
Hdu(L3)
66
1066
Voltage distortion (current value)
L3-N; THD
%
Hdi(L1)
68
1068
Current distortion (current value)
L1; THD
%
Hdi(L2)
70
1070
Current distortion (current value)
L2; THD
%
Hdi(L3)
72
1072
Current distortion (current value)
L3; THD
%
Temp
74
1074
Temperature (current value)
°C
Freq
76
1076
Frequency (current value)
Hz
P+tot
78
1078
Active power, recovery (counter status)
L1,L2,L3
kWh
P+ L1
80
1080
Active power, recovery (counter status)
L1
kWh
P+ L2
82
1082
Active power, recovery (counter status)
L2
kWh
P+ L3
84
1084
Active power, recovery (counter status)
L3
kWh
P-tot
86
1086
Active power, feed-back (counter status)
L1,L2,L3
kWh
P- L1
88
1088
Active power, feed-back (counter status)
L1
kWh
P- L2
90
1090
Active power, feed-back (counter status)
L2
kWh
P- L3
92
1092
Active power, feed-back (counter status)
L3
kWh
Q+tot
94
1094
Reactive power, recovery (counter status)
L1,L2,L3
kvarh
Q+ L1
96
1096
Reactive power, recovery (counter status)
L1
kvarh
Q+ L2
98
1098
Reactive power, recovery (counter status)
L2
kvarh
Q+ L3
100
1100
Reactive power, recovery (counter status)
L3
kvarh
Q-tot
102
1102
Reactive power, feed-back (counter
status)
L1,L2,L3
kvarh
Q- L1
104
1104
Reactive power, feed-back (counter
status)
L1
kvarh
Q- L2
106
1106
Reactive power, feed-back (counter
status)
L2
kvarh
Q- L3
108
1108
Reactive power, feed-back (counter
status)
L3
kvarh
U (N)
110
1110
Voltage (current value)
N
V
Modbus register current values/counter statuses Part 1