Operating panel devices
EST2 System Operations Manual 2.23
5. Enter the new password (nnnn).
Table 2-9: System passwords
Level Personnel Default Access Privileges
1 Operators 1111 All Status, Activate,
Restore, and Reports
functions
2 Supervisors 2222 All Level 1 privileges and
all Enable, Disable, and
Test functions
3 Administrators 3333 All Level 1 and 2
privileges and all program
functions.
Note: The system installer should change all passwords after the
system has been installed.
Programming the communications class
The fire alarm control panel receives the 64 panel addresses
listed below:
• 00: Primary power supply
• 01: MCM Signature detectors
• 02: MCM NACs and Signature modules
• 03: LCX Signature detectors
• 04: LCX NACs and Signature modules
• 05: Front panel LED/switch modules
• 06 through 09: Future use
• 10 through 63: Devices and accessories
To program a panel for Class A (Style 7) communications:
1. At the 2-LCD, press Program.
2. Press 4 to select communications class.
3. Enter a level 3 password.
4. Enter the panel address (pp).
5. Enter 1 to program the panel as a Class A (Style 7) circuit.