Operating panel devices
EST2 System Operations Manual 2.31
Activating system functions
This section explains the functions of the Activate switch. In the
Activate mode, the 2-LCD offers the following menu options:
Outputs
Actions
Sequences
Primary Smoke Sensitivity
Alternate Smoke Sensitivity
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.
Activating an output
To activate an output:
1. At the 2-LCD, press Activate.
2. Enter a level 1, 2, or 3 password.
3. Press 1 to select Output.
4. Enter the priority and address for the output device being
activated (PPppzz).
Activating an action
To activate an action:
1. At the 2-LCD, press Activate.
2. Enter a level 1, 2, or 3 password.
3. Press 2 to select Action.
4. Enter the number of the action being activated (nnnn).
Activating a sequence
To activate a sequence:
1. At the 2-LCD, press Activate.
2. Enter a level 1, 2, or 3 password.
3. Press 3 to select Sequence.
4. Enter the number of the sequence being activated (nnnn).