Operating panel devices
EST2 System Operations Manual 2.25
Enabling system functions
This section explains the functions of the Enable switch. In the
Enable mode, the 2-LCD offers the following menu options:
Zones
Messages
Time Controls
RS-485 Channels
Panels
Actions
Sequences
Laptop Computer Downloading
Mapping
Note: For a detailed explanation about the parameters of keypad
entries, see Making keypad entries, earlier in this chapter.
Enabling a zone
To enable a zone:
1. At the 2-LCD, press Enable.
2. Enter a level 2 or 3 password.
3. Enter 1 to select zone.
4. Enter the device address (ppzz).
Enabling a message
To enable a message:
1. At the 2-LCD, press Enable.
2. Enter a level 2 or 3 password.
3. Enter 2 to select message.
4. Enter the device address (ppzz).
Enabling a time control
Note: Do not enable more than 127 time controls at a time.
To enable a time control:
1. At the 2-LCD, press Enable.
2. Enter a level 2 or 3 password.
3. Enter 3 to select time control.
4. Enter the time-control numbers (tttt).

Table of Contents