the controller decreases the power supplied to the pump motor and the pump
speed decreases. If the r
otaonal speed of the pump decreases below 50% of the
full speed, the electronics can trip into a fail condion, depending on the system
conguraon. Refer to Timer on page 14.
▪ If the inlet pressure of the pump increases, the power supplied to the pump motor
increases to counteract the gas friconal load. When the built‑in maximum power
limit is reached, the speed of the pump starts to decrease. If the rotaonal speed
of the pump decreases below 50% of the full speed, the electronics can trip into
fail condion, depending on how the system has been congured. Refer to Timer
on page 14.
▪ If the electrical supply fails, the controller uses the motor in the pump as a
generator. This means the pump has its own regenerave supply and a separate
baery for an emergency power backup is not necessary. The regenerated energy
maintains the electrical supply to the controller, the vent valve or the fan aached
to the controller connector unl the pump speed decreases below 50% of the full
rotaonal speed to make sure that the vent valve stay shut unl below 50% of the
full rotaonal speed and prevent the pump from venng at a full speed. It makes
sure that the serial link and signals on the parallel interface stays acve unl the
pump speed decreases below 50%.
2.4 Operaonal features
The nEXT pumps have the basic start and stop commands and some other features that
allows the pump operaon to be modied for an applicable applicaon. Refer to Table:
Logic interface technical data for factory default sengs of the parameters given in the
secons that follows.
OEM supplied pumps can have drive parameters and default user‑selectable sengs.
The drive parameters and default user‑selectable sengs can be dierent from the
parameters given in the instrucon manual to suit specied process requirements.
Contact OEM for more informaon and advice.
2.4.1 Power limit seng
Select the maximum power that will be drawn by the pump. The more power supplied,
the quicker the pump will accelerate to reach full speed.
If the applicaon requires fast cycling or higher gas loads, set the power limit to the
maximum value. If ramp me is not important in the applicaon, use a lower power
limit, down to a minimum value (refer to Table: Power limit seng). Also ensure there is
sucient cooling for the applicaon.
Ensure that the power supply is capable of delivering sucient power to the nEXT pump.
By choosing a lower power limit seng, a smaller power supply may be used. For more
informaon, refer to Electrical data on page 29.
2.4.2 Standby speed
In standby mode, the pump rotaonal speed is lower than the full rotaonal speed. The
default seng for standby speed is 70% of the full speed.
To operate the pump at standby speed, it must be in the start condion.
04/2022 - ©Edwards Limited
Page 13B80000880_G
B80000880_G - Intr
oducon