42
Firmware version:
LCD Version:
11.2 APPLICATION SETTINGS
No Batteries: Allows access to Off-Grid mode when there is no battery and solar is the only
input available.
Power Backup: If Power Backup function is Enabled, the LOAD terminal will maintain output
when AC is interrupted. Set “Power Backup” via web/app (When enabling this mode, LOAD
output will be uninterrupted).
Seamless EPS switching: When power is interrupted, the inverter will turn to EPS mode
seamlessly unless there is a grid voltage fluctuation issue; in which case, we suggest you set
to “Disable” to avoid misjudgment.
Grid Sell Back: In some cases, the customer cannot feed energy into the grid. If the
customer does not want to/cannot feed energy to the grid, disable the Grid Sell Back
function.
Grid Sell Back Power(kW): If Grid Sell Back function is enabled, adjust the power limitation
to feed into the grid.
Fast Zero Export: Normally the inverter will adjust output power every 5 seconds to avoid
export. If Fast Zero Export is enabled, the inverter will adjust output power accordingly.
Off-Grid Mode: Allows for absolute zero-export, when there is an AC connection. When
enabled, the battery discharges power to load first and the grid will not assist in powering
loads and the batteries will not charge from AC unless “AC charge” is enabled.
PV Arc: The inverter will detect when there is a PV input Arc Fault and protect the inverter
from an Arc Fault.
PV Arc Fault Clear: Clears the records of PV Arc fault.
Grid Loss Warning Clear: Enable for an absolute Off-Grid system. The No AC Connection
and “AC V/F out of range” warnings will not occur when enabled.
RSD: Enable or disable the rapid shut-down detection of the PV inputs.
Normal/Standby: When set to Standby, there is no feed in, charge, nor discharge. Inverter
will need to be in Standby mode when you are changing most settings such as paralleling the
system. If this grid is available, the grid bypass relay will close, and the grid will take the load
normally (this setting is found above Application Setting on the app).
Restart Inverter
Micro-Grid: Only set this when generator is connected to the inverter’s Grid Terminal. With
this setting enabled, the inverter will use AC power to charge the battery and will not export
power.