Electrovert Aquastrom 200 - Exhaust Requirements

Electrovert Aquastrom 200
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Aquastorm 200
Overview 1-23
3.2 EXHAUST REQUIREMENTS
NOTE All exhaust measurements are
measured at the machine exhaust
port.
An independent, separate exhaust
blower is strongly recommended
for venting the Aquastorm 200™
due to the high volume
requirements as well as
condensate build up resulting from
normal operation of this
equipment.
For additional information on
specing a blower, contact your
local HVAC specialist for
requirements and ventilation
hook-up.
Recommended venting material - Seamless
stainless steel or PVC.
Two (2) 25.4 cm (10 inch) diameter exhaust ports
are provided at the top of the system.
Total system requires 72 M
3
/min. @ 2.5 cm
(2400 scfm @ 1") H
2
O static pressure.
Port #1 - 36 M
3
/min. @ 2.5 cm
(1200 SCFM @ 1.0" H
2
O)
static pressure.
Port #2 - 36 M
3
/min. @ 2.5 cm
(1200 SCFM @ 1.0" H
2
O)
static pressure.
Exhaust Locations
Port #1
Port #2