Aquastorm 200
13
13
Start-Up and Operation 3-13
Screen), the following will occur:
• Audible alarm sounds
• Alarm acknowledge indicator flashes
• Chemical isolation tank high temperature red
indicator illuminates
• Optional status tower flashes red
•LCD displays "Chemical Iso High Temp
Alarm"
• Tank heater is disabled
• System shuts down
If the tank's temperature falls below set point
temperature, by the value set for alarming (see
page 3-29 Alarm Process Screen), the following
will occur:
• Audible alarm sounds
• Alarm acknowledge indicator flashes
• Chemical isolation tank low temperature red
indicator illuminates
• Optional status tower flashes red
• LCD displays "Chem Iso Low Temp Alarm"
Normal operating temperature is indicated when
the green LED on the indicator is illuminated.
Rinse/Hurricane Pump
On/Off Control
Press the Rinse/Hurricane Pump On/Off
Control to activate the Rinse/ Hurricane pump.
The Rinse/Hurricane pump green on
indicator illuminates when the Rinse/
Hurricane Pump On/Off control is
pressed.
Press the Rinse/Hurricane Pump On/Off
Control again to deactivate the recirculating
pump.
Rinse JIC Pump On/Off
Control
The Rinse JIC Pump On/ Off control is not
applicable on the Aquastorm 200
™
series aqueous
cleaning system. This control is reserved for use
with the 300 series cleaner.
Chemical Isolation
Decrease Temperature
Control
Press the Chemical Isolation Decrease
Temperature Control to decrease the
temperature set point.
When pressed once and released, the
chemical isolation tank temperature set
point is decreased one (1) degree.
When the control is pressed and held, the
temperature set point is decreased until the
control is released.
NOTE Actual temperature and
temperature set points are visible
on the LCD.
Chemical Isolation Tank
High/ Low Temperature
Indicator
NOTE Only the Process Alarms
configured into the Process Alarms
screen with WARNING or SHUTDOWN
action selected will sound an audible
alarm.
Instructions provided here assume
WARNING or SHUTDOWN is selected
to sound an alarm.
Hardware configured alarms will always
sound when activated.
If the chemical isolation tank temperature
exceeds 82
o
C (180
o
F), the following will occur:
• Audible alarm sounds
• Alarm acknowledge indicator flashes
• Chemical isolation tank high temperature red
indicator illuminates
• Optional status tower flashes red
•LCD displays "Chemical Iso High Temp
Alarm"
• Tank heater is disabled
• System shuts down
If the chemical isolation tank temperature
exceeds set point temperature by the value set
for alarming (see page 3-29 Alarm Process