EasyManua.ls Logo

Electrovert Aquastrom 200 - SECTION 2 WEST 6700 TEMPERATURE CONTROL SETUP

Electrovert Aquastrom 200
170 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Aquastorm 200
2-6 System Preparation
SECTION 2 WEST 6700 TEMPERATURE
CONTROL SETUP
Refer to the West 6700 Temperature Control
illustration on this page to perform the
procedures outlined under the following headings:
2.2 To Enter Configuration Mode
2.3 To Enter Setup Mode
CAUTION The West 6700 controls are factory set
when installed into the Aquastorm
200™ system. Once installed, further
adjustment should not be required.
Improper adjustment could result in
damage to the equipment. This device
is a safety circuit. The procedures
outlined only apply to the replacement
of a defective unit, directly from stock.
WEST
6700
OUT
EXCEED
ALM
F
Function Key
Raise Key
Lower Key
Reset Key
Upper Display
Lower Display
Alarm Indicator
(NOT USED)
S
RESET
High or Low Limit
Exceed Indicator
West 6700 Temperature Control Illustration

Table of Contents