The coolers lights will remain on during saving mode.
considerations
Does not affect saving temperature.
Made available to ems55advanced GDCfirmware from June 2012.
Not used with OFCfirmware.
range 00 (off) or 01 (on)
global default 00 (off)
10.7 buzzer enable (b0)
The table below detail the buzzer enable (b0) parameter.
display
description
Enables or disables a warning buzzer for alarm conditions.
Door open alarms alwayssound the warning buzzer.
considerations
Following alarm conditions trigger the buzzer:
l
refrigeration system failure (rSF)
l
sensor failure (PF1, PF2, and PF3).
l gas cooler high temperature alarm
l CO2 lock out alarm
Door alarms sound the buzzer as standard.
range 00 (disabled) or 01 (enabled)
global default 01 (enabled)
10.8 buzzer duration (b1)
The table below details the buzzer duration (b1) parameter.
display
description
Defines the duration of the buzzer for door open alarm conditions.
If the door remains open after the buzzer duration (b1), the ems controller switches off the compressor.
considerations
The ems controller switches off the compressor after the duration defined by alarm delay (Ad) + buzzer
duration (b1).
range 1 to 254 seconds
global default 60 seconds
10.9 calibration 1 (CA1)
The table below details the calibration 1 (CA1) parameter.