perature rise quickly due to a door opening.
Increasing the value for the display stability (d2) slows the rate of change of the displayed temperature.
considerations Use the global default value for normal operation.
range 1 to 254
global default 2
10.13 defrost duration (dd)
The table below details the defrost duration (dd) parameter.
display
description Defines the maximum time of a defrost cycle.
considerations If icing up occurs, review the values of the defrost parameters.
range 1 to 199 minutes
global default 15 minutes
10.14 defrost interval (dE)
The table below details the defrost interval (dE) parameter.
display
description
Defines the period between the end of defrost cycle and beginning of the next defrost cycle. A time-
based defrost cycle helps improve evaporator efficiency.
considerations
l
In the event of power loss, the defrost duration (dE) is not maintained. The defrost interval is reset.
l If icing up occurs, review the values of the defrost parameters.
range 0 to 199 hours
global default 06 hours
10.15 differential (dIF)
The table below details the differential (dI F) parameter.
display
description
Defines the compressor cut-in temperature when added to the set point (SPC or S PF) temperature dur-
ing the ready mode.
considerations
If the differential (dIF) is set too low, for example, less than 2.0°Cthe compressor may cycle on the min-
imum compressor rest time (rt).
range 0.0 to 9.9°C (0 to 18°F)
global default 4.0°C (7°F)
ems25+ and ems25advanced / General Use