Above the saving set point (SSP) plus saving differential
(Sd) temperature.
l
Above the defrost termination (dtd) temperature.
range 0.0 to 30ºC (32 to 86ºF)
global default 20ºC (68ºF)
10.25 lights delay (Ld)
The table below details the lighst delay (Ld) parameter.
display
description Defines the delay to switch off the cooler lights after the ems controller switches to the saving mode.
considerations Must be set in multiples of 30.
range 0 to 120 minutes
global default 00 (no delay)
10.26 learning period (LP)
The table below details the learning period (LP) parameter.
display
description Defines whether the ems controller uses a 1-day or a 7-day learning period.
considerations None
range 00 (1 day) or 01 (7 days)
global default 00 (1 day)
10.27 saving temperature disable (PEr)
The table below details the saving temperature disable (PEr) parameter.
display
description
Disables the saving mode temperature so that the ems controller maintains the ready mode temperature
at all times.
Disabling the saving mode temperature does not affect the light functionality.
considerations None
range 00 (off) or 01 (on)
global default 00 (off)