Elstat ems25advanced - Defrost Duration (DD); Defrost Activation Temperature (Ddt); Defrost Interval (De)

Default Icon
89 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ems75sz: 3.0°C (5°F)
10.16 display (dIS)
The table below details the display (dI S) parameter.
display
description
Defines whether the ems controller displays the temperature 3.0, or the word USE during the ready
mode.
ems controllers always display alarms.
considerations None
range 00 (US E) or 01 (temperature)
global default 01 (temperature)
10.17 delay to saving (dS)
The table below details the delay to saving (dS) parameter.
display
description
Defines the delay in switching to the saving mode
from ready mode.
The delay starts at the end of the last active 30 minute
period of the ready mode.
considerations Must be set in multiples of 30 minutes.
range 0 to 120 minutes (in multiples of 30 minutes)
global default 00 (no delay)
10.18 defrost termination temperature (dtd)
The table below details the defrost temperature duration (dtd) parameter.
display
description
Defines the temperature to end the defrost cycle.
Ending defrost cycles on temperature minimizes the duration of defrost cycles.
The temperature is measured as follows:
l
OFC and sub-zero coolers: the temperature is measured on the evaporator sensor.
l
GDC coolers: the temperature is measured on the appliance sensor.
considerations
l
Must be set above the set point (SP) plus differential (dIF)temperature.
l
Must be set below IPd.
l If icing up occurs, review the values of the defrost parameters.
range 1 to 30ºC (33 to 86ºF)
ems25+ and ems25advanced / General Use
71 of 89