10.31 set point (SPC or SPF)
The table below details the set point (SPC or S PF) parameter.
display
description
Defines the compressor cut-out temperature during the ready mode. The set point (SP) temperature is
the lowest measured temperature under normal operating conditions.
The set point is displayed as S PC (set point Celsius) or SPF (set point Fahrenheit) depending on whether
the ems controller is set to use Celsius or Fahrenheit.
considerations Must be above the freeze-up protection (dtt) temperature.
range -9.9 to 9.9°C (14 to 50°F)
global default
3.0°C (37°F)
ems75sz: -3.0°C (27°F)
10.32 saving restart period (Sr)
The table below details the saving restart period (Sr) parameter.
display
description
Defines the maximum time allocated to reach the set point (SP) temperature from the saving mode tem-
perature.
considerations
l Set and verified by OEMs through the test protocol to ensure that product temperatures are within specification
when outlets open.
l Must be set in multiples of 30 minutes.
range 0 to 240 minutes (in multiples of 30 minutes)
global default 120 minutes
10.33 saving set point (SSP)
The table below details the saving set point (SSP) parameter.
display
description Defines the compressor cut-out temperature during the saving mode.
considerations Must be set above the set point (SP) plus differential (dIF)temperature.
range
0.0 to 9.9°C (32 to 50°F)
ems75sz: -9.9 to 9.9°C (14 to 50°F)
ems25+ and ems25advanced / General Use
76 of 89