Partial scan, only add new devices - scans for newly added DALI devices to the selected
gateway without assigning short addresses. Missing devices are not removed from the list
Port settings serial port name if there are external DALI-RS-485 interfaces connected
Note! Make sure Modbus RTU is not enabled for the same RS-485 if you are using external DALI
-485 port.
Note! Make sure you have series connection for all DALI gateways.
Note! In case you have long RS-485 lines between LM and DALI gateway, make sure to use 120
Ohm termination resistors on LM and on the farthest DALI gateway.
Note! Make sure GND are connected (if you use separate power supplies for LM and DALI gw)