Section 7: Parameter Menu
Parameter Menu
7.3 Parameter Group: Speed
Table 6. Speed Parameter Group
Menu item
Sub Menu
item
Poss.
Setting
2)
Notes / Comments
P4.1 Speed Local Open
2,5 -
72,2min
−1
Output speed for local operation in direction OPEN
P4.2
Speed Local Close
2,5 -
72,2min
−1
As P4.1 but in direction CLOSE
P4.3 Speed Remote Open
2,5 -
72,2min
−1
Output speed for remote operation in direction OPEN
P4.4 Speed Remote Close
2,5 -
72,2min
−1
As P4.3 but in direction CLOSE
P4.5 Speed
Emergency
Open
2,5 -
72,2min
−1
Output speed for emergency operation in direction OPEN
P4.6 Speed
Emergency
Close
2,5 -
72,2min
−1
As P4.5 but in direction CLOSE
P4.7 Speed
Torque-
dependent.
2,5 -
72,2min
−1
seal-tight speed. Speed at which the actuator runs near
the end position at torque-dependent switch off
(see P1.3 u. P1.4)
P4.8 Speed Minimum
2,5 -
72,2min
−1
Minimum speed
CAUTION: NOTE MAXIMUM SPEED LIMITS
the max. speed for the 24VDC actuator version is reduced to 20min
−1
7.4 Parameter Group: Ramp (option)
The start ramp can be set separately for each operation mode. Thus, a 100% start ramp
means that the motor attains its maximum speed in about a second. Higher speeds
(see Section 7.3) lead to shorter runtimes. If the ramp is set below 100%, the starting time
increases in an inversely proportional fashion.
Table 7. Ramp Parameter Group
Menu Item Sub Menu Item
Poss.
Setting
Notes / Comments
P5.1 Ramp Local 5 - 100% Start ramp for local operation
P5.2 Ramp Remote 5 - 100% Start ramp for remote operation
P5.3 Ramp Emergency 5 - 100% Start ramp for emergency operation