Section 7: Parameter Menu
Parameter Menu
Table 17. Position Output Parameter Group (2)
Menu item
Sub Menu
Item
Poss.
Setting
Notes / Comments
P11.2 Position Output Start (at 0%)
0 - 20,5
mA {4mA}
mA value for the Closed (0%) position
P11.3 Position Output End (at 100%)
0 - 20,5 mA
{20mA}
mA-value for the On (100%) position
P11.4 Position Output Calib. 20mA
-10% -
+10%
Calibrating the output position during the setting of
this parameter will output a 20mA (100%) signal. Use
this parameter to calibrate accurately the 20mA output
signal. (e.g., if you measure 19.8 mA at the output, just
add 1% (0.2 mA. . . 1% of 20mA) to the displayed value)
P11.5 Analog Output Function 2
see
Function 1
P11.6 Analog Output Start (at 0%) see Start
P11.7 Analog Output End (at 100%) see End
P11.8 Analog Output Calib. 20mA Calib. 20mA