EasyManua.ls Logo

Emerson Liebert NXL - Figure 40 Liebert NXL 1100 Kva, Single Module System, Shipping Split-Power Wiring

Emerson Liebert NXL
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Drawings
53
Figure 40 Liebert NXL 1100kVA, single module system, shipping split—Power wiring
BUSBAR (INPUT TO RECTIFIER)
(1) PLACE PHASE B ONLY
SAME CONNECTION IN
INPUT CABINET SEE PG 3
INSTALL M10X45 CARRIAGE BOLT (12)
M10 LARGE FLAT WASHER (12)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (12)
TORQUE TO 27Nm (240 in-lb)
BUSBAR
(RECTIFIER POS TO DC CABINET POS)
INSTALL M10X60 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
(INPUT CONNECTION)
INSTALL M10X45 CARRIAGE BOLT (3)
M10 LARGE FLAT WASHER (3)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (3)
TORQUE TO 27Nm (240 in-lb)
REMOVE THIS HARDWARE AND
INSULATOR AND INSTALL BUS,
THEN INSTALL INSULATOR AND
HARDWARE AS SHOWN
INSULATOR
BUS
INSTALL M10X45 CARRIAGE BOLT (6)
M10 LARGE FLAT WASHER (6)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (6)
TORQUE TO 27Nm (240 in-lb)
(NOTE: SOME HARDWARE NOT SHOWN THIS VIEW)
POSITIVE DC BUS LINK
INPUT CABINET
RECTIFIER CABINET
DC CABINET
INVERTER CABINET
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
(POSITIVE DC CONNECTION)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
(NEGATIVE & POSITIVE DC CONNECTION)
(NEGATIVE & POSITIVE DC CONNECTION)
BUSBARS
(DC CABINET TO INVERTER CABINET)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
INSTALL M10X45 CARRIAGE BOLT (2)
M10 LARGE FLAT WASHER (2)
(2) M10 BELLEVILLE WASHERS PER BOLT
M10 NUT (2)
TORQUE TO 27Nm (240 in-lb)
BUSBARS
(DC CABINET TO
INVERTER CABINET)
NOTES:
1. EXTRA HARDWARE PROVIDED
FOR POWER CONNECTIONS.
POSITIVE DC BUS LINK
RECTIFIER CABINET
DC CABINET
INVERTER CABINET
BUSBAR
(RECTIFIER NEG TO DC CABINET NEG)
FLEX BUS
(INPUT TO RECTIFIER)
(2) PLACES PHASE A & C ONLY
SAME CONNECTION IN
INPUT CABINET SEE PG 3
DETAIL H (TOP)
DETAIL A
A
DETAIL B
B
DETAIL C
C
DETAIL D
D
DETAIL E
E
DETAIL F
F
DETAIL H
H
DETAIL G
G
B

Table of Contents

Related product manuals