Specifications
64
Physical Parameters and Standards, in (mm)
Width, With Static Bypass 140.5 (3568.7) 228.3 (5798.8)
Width, without Static Bypass 125 (3175) 197.5 (5016.5)
Depth 39.4 (1000.7) 46.1 (1170.9)
Height 76.8 (1950.7) 78.7 (1999)
Weight, Unpackaged, lb. (kg) approx.,
with Static Bypass (SMS) 13,650 (6191.5) 21,450 (9730)
with Static Bypass (1+N) 13,100 (5942) 21,800 (9888)
without Static Bypass (N+1) 13,800 (6260) 20,050 (9095)
Maximum Heat Dissipation, Full Load, BTU/hr 167,265 252,540
Cooling Air, CFM 15,760 8,700
Color Black (ZP-7021)
Front Door Opening (for serviceability) More than 180°
Degree of Protection for UPS Enclosure IP 20 (with and without front door open)
Minimum Clearance, Top, in (mm) 24 (610)
Minimum Clearance, Back, in (mm) 0
Minimum Clearance, Sides, in (mm) 0
Location of Cable Entrance Top or Bottom
Standards and Conformities
UL 1778, 4th Ed.
CSA 22.2 107.3
FCC Part 15, Class A
IEC62040-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6, Level 4, Criteria A
EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3
ISTA Procedure 1H
WEEE
Environmental Parameters
Storage Temperature Range, °F (°C) -13 to 158 (-25 to 70)
Operating Temperature Range, °F (°C) 32 to 104 (0 to 40) (UPS)
Relative Humidity
95% or less
Non-Condensing (Operating and Non-Operating)
Maximum Altitude Above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) - 1% Maximum kW derate / 328
rise
between 4921-9842 (100m rise between 1500-3000m)
Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
Depth dimensions include the front door and rear panel.
Table 11 Liebert NXL UPS specifications (continued)