Specifications
70
Bonding
UPS Rating
Voltage, VAC Nominal Selection (#) Conduit Size, Ph, G kVA kW
625 625 480 (1) 250kcmil/ (1) 250kcmil
625 625 575
(1) 250kcmil/ (1) 250kcmil
625 625 600
(1) 250kcmil/ (1) 250kcmil
1100 1100 480 (1) 350kcmil/ (1) 350kcmil
1100 1100 575 (1) 350kcmil/ (1) 350kcmil
1100 1100 600 (1) 350kcmil/ (1) 350kcmil
1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient.
2. For continuous operation not at 86°F (30°C), Emerson recommends that the site planner choose
the appropriate cable type based on the particular installation requirements.
Table 16 Recommended conduit and cable sizes (continued)
Rectifier Input
UPS Rating
Voltage, VAC Nominal Selection (#) Conduit Size, Ph, GkVA kW